MIL-HDBK-1001/SA
will shrink while losing water and the shrinkage strain could be transmitted to the roof membrane, do not fully adhere thick pads directly to the roof surface. Adhered modified bitumen sheets or precut pavers placed on filter fabric may also be used.
10.4.8 Cold-Process Roofing. Cold-process systems are life extension and maintenance procedures on smooth roofs. There are coating and overlay types in asphalt or coal tar base with or without reinforcement. They must be placed on clean, dry surfaces with no entrapped wet insulation below.