MIL-HDBK-1003/1
108.6 Abatement of Violation. (Deleted in its entirety.)
108.7 Unsafe Plumbing Systems. (Deleted in its entirety.)
SECTION 109
MEANS OF APPEAL
109.1 Application for Appeal. The construction contractor will have the rights granted by the Contracts Disputes Act of
1978 and the Disputes clause of the contract.
109.2 Membership of Board. (Deleted in its entirety.)
109.3 Notice of Meeting. (Deleted in its entirety.)
109.4 Open Hearing. (Deleted in its entirety.)
109.5 Postponed Hearing. (Deleted in its entirety.)
109.6 Board Decision. (Deleted in its entirety.)
109.7 Court Review. (Deleted in its entirety.) End of revised Chapter 1 Administration.
SECTION 301.6 Prohibited Locations. Insert after the last
sentence, and before the Exception: "No plumbing system components may be installed within any Air Handling Unit (AHU), ductwork, or room used as a plenum conveying supply air, return air, outside air, or mixed air. This will not
prohibit connection of AHU components, such as humidifiers, to
the water supply system, nor prohibit connection of trapped
condensate pans and humidifier drains indirectly to the
drainage system."
Add "SECTION 301.7 Protection of Building Materials. Where the seasonal design temperature of the cold water entering a building is below the seasonal design dew point of the indoor ambient air, and where condensate drip will cause damage or create a hazard, insulate plumbing piping with a vapor barrier type of insulation to prevent condensation. All chilled water
16