MIL-HDBK-1003/1
piping from a central drinking water cooling system should be insulated with vapor barrier type insulation to prevent condensation."
SECTION 305.6 Freezing. Add after the last sentence: "Although insulating water pipes, tanks, and cooling tower may not prevent water from freezing, these devices are to be insulated and possibly heat traced for protection against damage. The proper thickness or conductivity factor for this insulation is to be determined by the design engineer."
Add "SECTION 313 Energy Conservation. Design systems containing solar water heaters, air-to-water heat pump water heaters, and water-to-water heat pump water heaters in accordance with the ASHRAE Handbook Series, appropriate Chapters; and ASHRAE Standard 90.1."
SECTION 403.1 Minimum Number of Fixtures. Add additional
Notes beneath IPC Table 403.1 as follows:
"For use in Navy facilities: (prevails when in conflict with Table 403.1 and notes above).
g For "male only" toilet facilities, urinals may be substituted for no more than one-third of the water closets required, one for one.
h For "Assembly" occupancies, provide drinking fountains at
1 per 400 persons.
i For "Business" (office, public buildings, and similar,
and for bowling centers); "Educational" (Training); "Factory and Industrial" (Industrial, shops, warehouses, and
similar), provide fixtures (both male and female) at the following rates:
(1) water closets 1 per 20 persons (p), up to 100 p; then 1 per 40 p.
(2) lavatories 1 per 20 p, up to 100 p; then 1 per 45p.
(3) showers 1 per 15 p - Only if needed. (4) drinking fountains 1 per 75 p.
17