MIL-HDBK-1003/1
closets are being served. When duplex pump units are provided, the capacity of each pump is to be sufficient to meet the requirements of the facility."
SECTION 712.3.2 Sump Pit. Add the following. "Sumps are to contain, in gallons, between the high level and low level operating switch settings approximately twice the capacity of the sump pump, in gallons per minute."
SECTION 712.3.4 Maximum Effluent Level. Add the following. "A high water alarm actuator is to be installed within sump and operate an audible or visual alarm when the normal high- water level within sump has been exceeded."
Add "SECTION 712.3.6 Controls. Automatic controls are to be provided for each pump. Duplex pump units are to be equipped with controls to alternate the operation of the pumps under normal conditions and to operate pumps simultaneously when one pump cannot handle the flow."
SECTION 9.17 AIR ADMITTANCE VALVES. Delete in its entirety. Revise SECTION 1003.1.1 Interceptor Not Required. To read as
follows: "An interceptor should not be required or provided
for individual dwelling units or any private living quarters."
SECTION 1003.5 Interceptors Required. Add the following. "Grease interceptors should be provided to receive the wastes from pot sinks, pre-wash sinks, dishwashers without pre-wash sections and soup kettles."
SECTION 1104.2 Combining Storm with Sanitary Drainage. Add the following. "When a combined drainage system is to be provided, the systems should be maintained as separate systems within the building. Systems should be combined outside of
the building and preferably at a manhole."
Add "SECTION 1104.4 Insulation of Rainwater Conductors. To prevent condensation, insulate horizontal conductors and roof drains inside the building."