IL-HDBK-1003/1
TYPICAL EXISTING OR NEW HAZMAT CURB OR BERM
1.8 SLOPE MAXIMUM
ES/EWS CURB, 4• WIDE CREST, SLOPED TO FLOOR
1"X1" RIBBED FIBERGIASS (FG) CONC. ANGLE
1-1/2"X1-1/2iC1" THK FG GRATE,
36i<36" SQ., WITH SUP RESISTANT SURFACE
NON-SLIP SURtACE il�:-�::.:;:�/i�:::c�Qt::;lf7�
--J--T-tR'a&-[i-- . ,.,,-..,·-URB HEIGH.r-- F.O. W/4" DEEPSEAL TRAP
ES/EWS CURB SECTION
N.T.S.
000 000 000
RAMP UP RAMP UP
l:8 SLOPE MAX.
RAMP UP 1
ES/EWS CURB PLAN VIEW
N.T.S.
OPTIONAL, SEE GENERAL NOTE 2.
GENERAL NOTES,
EMERGENCY SHOWER & EYE WASH (ES/EWS) DETAIL
N.T.S.
1. DETAILS SHOWN NOT TO SCALE.
2. DESIGNER SHALL DETERMINE ALARM, LIGHTING ANO MONITORING REQUIREMENTS.
3. tLOOR DRAIN (FD) IS OPTIONAL, SEE ES/EWS rrc.
4. IF FD PROVIDED7PROVIDE MINIMUM ES/EWS FD CURB
HEIGHT • I -1 2 INCHES.
5. FOR ES/EWS WITH FD. WITHIN A HAZMAT CURBED OR BERMEO AREA, PROVIDE ES/EWS FU CURB
HEIGHT= HAZMAT CURB HEIGHT PLUS 1-1/2 INCHES. TO ENSURE NO HAZMAT SPILL ENTERS THE FD.
6. PROVIDE FREEZE PIROTECTION, WHERE NECESSARY.
7. PROVIDE SHOWER CURTAIN ANO SUPPORT ROD. FOR INDOOR USE.
8. PROVIDE ENCLOSURE FOR OUTDOOR USE, DRAIN TO A CURSED OR BERMEO AREA.
9. IF FLOOR DRAIN IS NEEDED OIJTDOORS, PROVIDE AN ES/EWS FD, CURB & GRATING, TO EXCLUDE STORM WATER FROM ENTERING TO FLOOR DRAIN.
35
Source: https://assist.dla.mil -- Downloaded: 2014-09-28T13:51Z Check the source to verify that this is the current version before use.
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business