MIL-HDBK-1036A
(3) Bathtubs: 1 per 8 persons
(4) Showers: 1 per 8 persons
(5) Water coolers: 1 per 100 persons
(6) Service sinks: one floor or service area.
4.49 Electrical
a) Provide the following as required: (1) Distribution equipment
(2) Wiring
(3) Receptacles and grounding
(4) Interior and exterior lighting
(5) Emergency lighting
(6) Telephone wiring
(7) Fire detection and annunciation
(8) Cable television wiring
doors.
(9) Intrusion detection systems at the exterior
(10) Ceiling fans, see Table 3 and par. 4.37.
b) Base electrical system design calculations on multi-family occupancy rather than interior corridor occupancy since the bachelor housing is the full-time home of the residents, and therefore has a higher demand factor.
c) Provide metering for electric power.
d) For direct entrance rooms, provide three-way switches at the entrance door and in the vanity area so that the living room and bedroom area lighting is controlled at either location. Also, provide motion sensor switches at bathroom doors to control the bathroom light fixture. Provide 20 ampere outlets throughout the apartment per applicable electrical code. In